|
EXTINGUISHERS
(Types
of Extiguishers)
General
Extinguishers
are essentially first aid fire fighting appliances.
Nevertheless,
these are very valuable if used promptly and efficiently in
the early stages of a fire. In addition to the value of their
portability, the most important feature of these extinguishers
is their immediate availability so that each extinguisher
can be used by one person.
The usefulness of these extinguishers is limited as it is
entirely dependent upon the presence of persons having knowledge
to operate them. Furthermore their capacity is also limited
and their operational value largely depend upon the initial
charge being sufficient to overcome and confine the fire.
The capacity of such extinguishers should be commensurate
with the risk these are intended to cover.
Since
a variety of shapes or methods of operation of fire extinguishers
have at times, led to confusion, and failure to quench the
fire, it is recommended that extinguishers installed in any
one building or single occupancy shall be similar in shape
and appearance and should have the same method of operation,
as far as possible. This will also simplify the training of
the large number of workers in the effective and efficient
use of extinguishers.
Number
& Size Of Fire Extinguishers
Fire
extinguishers shall be provided both for protecting building
structure as well as occupancy hazard contained therein.
The
number and size of fire extinguishers required for any particular
premises shall be determined by the appropriate authority
taking into consideration the severity of incipient fire anticipated,
rapidly with which a fire may spread, intensity of heat that
may be developed, accessibility to fire, type of extinguisher,
the smoke contributed by the burning material, special features
of building construction and nature of occupancy (single or
mixed), and electrical fittings, equipment etc., installed
therein.
The
required number of portable fire extinguishers may be determined
by considering any single extinguisher of suitable type or
a combination of two or more types. Recommendations made in
Appendix A may be taken as a guide.
Selection
Of Location
When
selecting locations for fire extinguishers, due consideration
should be given to the nature of risk to be covered. The extinguishers
should be placed in conspicuous positions and shall be readily
accessible for immediate use in all parts of the occupancy.
It should always be borne in mind while selecting locations
that fire extinguishers are intended only for the use on incipient
fires and they will be of little value if the fire is not
extinguished or brought under control in the early stages.
Generally,
portable fire extinguishers should be placed as near as possible
to exits or stair landings wherever possible, advantage
should be taken of normal routes of escape by placing these
in positions where these shall readily be seen by persons
following the natural impulse to get out of danger.
It
is not advisable to place extinguishers at the ends of rooms
remote from exits unless such distribution is necessary to
cover a particular hazard. The extinguisher should be visible
and easily accessible and the passage leading to them should
always be kept completely unobstructed.
A
framed plan showing the location of fire extinguishers, means
of access and other useful information should be displayed
at suitable places.
Installation
General
Although
portable fire extinguishers are not permanent and immovable
fittings in a structure, these form a part of the whole system
of fire protection and should receive consideration at the
design stage. In some cases, it may be necessary for the extinguishers
to be housed in readily accessible and unlocked receptacles,
where although clearly visible, these should be unobtrusive.
Cognizance should be taken of any statutory order, local by-law
or other requirements with which compliance is essential.
Time
Schedule
Excepting
particular cases where, as stated in a), it may be necessary
for the extinguisher to be housed in specially prepared positions,
no structural work is generally involved in the installations
of the extinguishers dealt with in this standard as this normally
takes place upon the completion of the construction. The General
sequence of the building operation is not, therefore, usually
effective. Where a special recess is to be formed in a wall,
provision should be made as the work progresses.
Selection
Of Fire Extinguishers
Various
types of fire extinguishers specified in this standard are
of value but are all not equally effective on all types of
fire. For this reason, the nature of contents of a building,
the process carried out therein and the types of fire, which
may occur, shall be taken into consideration while selecting
fire extinguishers.
For
all practical purposes the basic types of fires can be grouped
into following four classes :
Fires
involving combustible materials of organic nature, such as
wood, paper, rubber and many plastics etc., where the cooling
effect of water is essential for extinction of fires.
Fires
involving flammable liquids, petroleum products, or the like,
where a blanketing effect is essential.
Fires
involving flammable gases under pressure including liquefied
gases, where it is necessary to inhibit the burning gas at
fast rate with an inert gas, powder or vaporizing liquid for
extinguishment.
Fires
involving combustible metals, such as magnesium, aluminium,
zinc, sodium, potassium, when the burning metals are reactive
to water and water containing agents, and in certain cases
carbon dioxide, haloginated hydrocarbons and ordinary dry
powders. These fire required special media and techniques
to extinguish.
Suitability
Of Portable Fire Extinguishers
The
types of extinguishers mentioned below against each class
of fire are generally most suited. Details of suitability
as a guide of each type of extinguisher is shown in Table
I. It may, however, be noted that this is only for guidance
and does not cover special cases.
Water
expelling type extinguishers.
Foam,
dry powder, vaporizing liquid (at present there is no Indian
Standard covering this type), carbon dioxide extinguishers.
Dry
powder and carbon dioxide extinguishers.
Extinguishers designed for expelling special dry chemical
powder.
Work
On Site
Work
on site mainly consists of charging the extinguishers where
necessary, and placing these at appropriate location.
Each
new extinguisher should be charged with the ' refill ' provided
with it in accordance with the instruction given on the refill
container. This however does not apply to the carbon dioxide
extinguishers which are available fully charged.
All
refills should conform to relevant Indian Standards.
All
bucket pump type extinguishers should be filled with clean
water before being placed in position.
All
new extinguishers should be wiped clean from the outside and
the brass parts should be polished with metal polish. Care
should be taken to ensure that the nozzle outlet or the vent
holes provided in the screwed portion of the cap or shifter
valve or vent holes, if provided, do not get clogged.
Where
applicable, hose and nozzle connections should be checked
to ensure tightness of joints.
Each
first aid fire extinguishers should be allotted a special
number by which it shall be referred to in the records. The
following details should be painted with white paint on the
body of each fire extinguisher :
- Serial
number,
- Date
of last refilling, and
- Date
of last inspection.
The
details should be repainted each time the extinguisher is
refilled or inspected.
Once
the location of each extinguisher is decided, these should
be fixed or placed in position as given below :
- In
Open Area
Fire
extinguishers should be placed on masonry platforms or in
wooden or metal cabinets in such a way that their bottom is
750 mm above the ground level.
Where
cabinets or sheds are used to house the extinguishers in the
open, these should be so designed that removal of these extinguishers
are not hampered in an emergency.
- Inside
a Building and Under Cover
Fire extinguishers whether hung on brackets or kept on shelves
should have their bottom 750-mm above the floor level.
In
no case a fire extinguisher should be places in a position
where it is likely to gain heat from the surrounding equipment
or the process.
TABLE
- I
Suitability
Of Different Types Of Fire Extinguishers For Different Class
Of Fires
|
Type
of Fires |
| Type
of Extinguisher |
A |
B |
C |
D |
| Fire
extinguisher, soda acid, IS:934-1976 |
S |
NS |
NS |
NS |
| Fire
extinguisher water type, gas cartridge, IS:940-1976 |
S |
NS |
NS |
NS |
| Water
type bucket pump, IS:1924-1975 |
S |
NS |
NS |
NS |
| Water
type stored pressure, IS:6234-1971 |
S |
NS |
NS |
NS |
| Fire
extinguisher chemical foam, IS:933-1976 |
S |
S |
NS |
NS |
| Fire
extinguisher dry powder, IS:2171-1976 |
NS |
S |
S |
@NS |
| Fire
extinguisher carbon dioxide type, IS:2878-1976 |
NS |
S |
S |
NS |
|
| S |
For
suitable |
| NS |
For
not suitable |
| @ |
Suitable
if special dry powder for burning metal is used |
Maintenance,
Inspection And Testing
Routine
maintenance, inspection and testing of all fire extinguishers
in respect of mechanical parts, extinguishing media and expelling
means should be carried out by properly trained personnel
at frequent intervals but atleast once in a month to make
sure that these are in their proper condition and have not
been accidentally discharged or lost pressure or suffered
damage.
At
a longer interval, atleast once in a year, a more thorough
inspection and maintenance of extinguisher, including chemical
charge inside and expellent should be carried out by trained
personnel, according to the procedure given below for each
type of extinguisher separately. Any extinguisher showing
corrosion or damage to the body internally or externally should
be replaced. Faulty, damaged and corroded parts shall be replaced
by correct component. Illegible labels should be replaced.
The
inspection and maintenance of extinguisher is designed to
ensure that the extinguisher will remain as reliable during
the whole service as when new. But it is not desirable that
extinguisher should remain in service indefinitely without
more thorough test as in some cases, such as chemical foam,
dry powder etc., the extinguishing media itself is liable
to deteriorate and should be periodically replaced.
The
performance tests on 50 percent of each type of extinguisher
shall be carried out in accordance with relevant Indian Standard
at intervals.
The
pressure or leakage test of all types of extinguishers shall
be carried out at intervals.
The
rejected bodies of the extinguishers should be destroyed,
so as to prohibit their subsequent use.
Records
The
records of maintenance, inspection and testing of all first-aid
fire extinguishers should be maintained in the register (Appendix
B). One page should be allowed to each extinguisher.
A
P P E N D I X - A
Recommended
Scale Of Portable Fire Extinguishers For Different Types Of
Fire Risks
| Type
of Fire risk and Nature of Occupancy |
Examples
of Occupancies |
Scale
of equipment |
|
Class
'A' fires, light hazard or low fire load normal occupancies
|
Offices
(other than record rooms), schools, assembly halls,
canteens, clubs, recreation rooms, places of worship,
boarding houses etc.
|
For
every 600 m2 of floor area or part thereof
one 9 ltr water expelling extinguisher with a minimum
of two extinguishers per compartment/floor of the building.
The extinguishers shall be so distributed over the entire
area that a person shall have to travel not more than
25 m from any point to reach the nearest extinguisher.
|
|
Class
'A' fires, ordinary hazard or low fire load abnormal
occupancies
|
Ordinary
record rooms, general merchandise shops, book binders,
small store rooms, tailoring shops, small timber yards
etc.
|
For
every 600 m2 of floor area or part thereof
one 9 ltr water expelling extinguisher with a minimum
of two extinguishers per compartment/floor of the building.
The extinguishers shall be so distributed over the entire
area that a person shall have to travel not more than
15 m from any point to reach the nearest extinguisher.
|
|
Class
'A' fires, extra hazards or high fire load occupancies
|
Large
timber yards, saw mills, godowns and warehouses storing
combustible materials, flour mills etc.
|
The
same as given in Sl. No. (ii). However, in such cases
extra provision shall be made in consultation with local
fire authority.
|
|
Class
'A' fires, special hazards
|
Important
office records, service documents, archives, libraries,
data processing centres, museums etc.
|
For
every 100 m2 of floor area or part thereof
one 4.5 kg carbon dioxide extinguisher with a minimum
of two extinguishers per room/compartment. The extinguishers
shall be so distributed over the entire area that a
person shall have to travel not more than 10 m from
any point to reach the nearest extinguisher.
|
|
Class
'B' fires, storage and handling in small quantities
generally in mixed occupancies.
|
Workshops,
garages, painting shops, general stores, cook houses
etc.
|
Two
extinguishers (9 litre foam or 5 kg dry powder) per
50 m2 of floor area or part thereof. The
extinguishers shall be so distributed that a person
shall have to travel not more than 10 m from any point
to reach the nearest extinguisher.
|
|
Class
'B' fires, bulk storage other than in tank firms
|
Flammable
liquid stores, storage in drums/cans in open, paint
and varnish godowns etc.
|
Per
100 m2 of floor area two extinguisher (9
litre foam or 5 kg dry powder) with a minimum of three
extinguishers per room/compartment/stock. The extinguishers
shall be so distributed over the entire area that a
person shall have to travel not more than 10 m from
any point to reach the nearest extinguishers.
|
|
Class
'B' fires, bulk storage underground completely covered.
|
Public
petrol/diesel/kerosene pumps and other similar storage
in industries.
|
Three
extinguishers (9 litres foam or 5 kg dry powder) per
pumping set.
|
|
Class
'C' fires
|
Storage
and handling of gas cylinders, gas plants, small gas
holders and gas lines passing through buildings etc.
|
For
every 100 m2 of floor area or part thereof,
two 10 kg dry powder extinguisher or 6 kg carbon dioxide
extinguisher subject to a minimum of three extinguishers
of same type per room/ compartment. The extinguishers
shall be so distributed over the entire area that a
person shall have to travel not more than 10 m from
any point to reach the nearest extinguishers.
|
|
Class
'D' fires
|
All
process involving the use of combustible metals, storage
of such metals, their clippings and powders.
|
Two
5 kg fire extinguisher special dry powder for every
50 m2 of floor area or part thereof subject to a minimum
of three extinguishers per room/compartment. The extinguishers
shall be so distributed over the entire area that a
person shall have to travel not more than 10 m from
any point to reach the nearest extinguishers.
|
|
Mixed
occupancies (electrical risks)
|
Workshops,
generators, transformers, electric motors, switch gear,
battery, charging rooms, transmitting and receiving
stations, T.V. centre, air conditioning plants, X-ray
rooms, operation theatres, telephone exchanges, cinema
projection rooms, photo sections, instrument calibration
and standards rooms, laboratories, all types of delicate
electronic equipment, computer rooms etc.
|
For
100 m2 of floor area or part thereof, one extinguisher
(10 kg dry powder or 6 kg carbon dioxide) with a minimum
of two extinguishers of same type per room/compartment/group
of machines.
|
Types
And Capacity Of Various Extinguishers
| Type
Of Extinguishers |
Capacity |
| Soda
Acid |
9
Ltrs, 50 Ltrs., 150/160 Ltrs. |
| Foam |
9
Ltrs., 50 Ltrs., 150 Ltrs. |
| Dry
Chemical Powder |
1
kg., 2 kg., 10 kg., 25 kg., 50 kg., 75 kg. |
| Carbon
Dioxide |
2
kg., 3 kg., 4.5 kg., 6.5 kg., 9 kg., 22.5 kg. |
| Mechanical
Foam |
9
Ltrs. |
| Water
CO2 |
9
Ltrs. |
| BCF
Halon |
1.25
kg., 2 kg., 2.5 kg., 3 kg., 3.5 kg., 4 kg., 4.5 kg., 5
kg. |
| Automatic
Modular Halon |
5
kg., 10 kg., 15 kg. |
| Automatic
Modular DCP |
5
kg., 10 kg., 15 kg. |
|